ATV630C22N4 inverter, 220kw ATV630

ATV630C22N4 inverter, 220kw ATV630

Share to:

Aditional Informations

PRODUCT INFORMATION OF SCHNEIDER ATV630C22N4 inverter, 220kw ATV630 spot free shipping

 

Main

Range of product Altivar Process ATV600
Product or component type Variable speed drive
Product specific application Process and utilities
Device short name ATV630
Variant of ATV630C22N4 inverter Standard version
Product destination Asynchronous motors
Synchronous motors
EMC filter of ATV630C22N4 inverter Integrated with 50 m conforming to EN/IEC 61800-3 category C3
IP degree of protection IP00 conforming to IEC 61800-5-1
IP00 conforming to IEC 60529
IP21 (with kit VW3A9112) conforming to IEC 61800-5-1
IP21 (with kit VW3A9112) conforming to IEC 60529
[Us] rated supply voltage 380…480 V
Type of cooling Forced convection
supply frequency 50…60 Hz – 5…5 %
[Us] rated supply voltage 380…480 V – 15…10 %
motor power kW 160 kW (heavy duty)
220 kW (normal duty)
motor power hp 350 hp normal duty
250 hp heavy duty
line current 397 A at 380 V (normal duty)
324 A at 480 V (normal duty)
296 A at 380 V (heavy duty)
246 A at 480 V (heavy duty)
Prospective line Isc 50 kA
apparent power 247 kVA at 480 V (normal duty)
187 kVA at 480 V (heavy duty)
continuous output current 302 A at 2.5 kHz for heavy duty
427 A at 2.5 kHz for normal duty
maximum transient current 453 A during 60 s (heavy duty)
470 A during 60 s (normal duty)
Asynchronous motor control profile Constant torque standard
Variable torque standard
Optimized torque mode
Synchronous motor control profile Permanent magnet motor
Synchronous reluctance motor
Speed drive output frequency 0.1…500 Hz
Nominal switching frequency 2.5 kHz
switching frequency 2.5…8 kHz with derating factor
2…8 kHz adjustable
safety function STO (safe torque off) SIL 3
Discrete input logic 16 preset speeds
Communication port protocol Modbus TCP
Ethernet
Modbus serial
option card of ATV630C22N4 inverter Slot A: communication module, Profibus DP V1
Slot A: communication module, PROFINET
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/EtherNet/IP
Slot A: communication module, CANopen daisy chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw terminals
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink
Mounting mode Wall mount
Network number of phases 3 phases
Discrete output number 0
discrete output type Relay outputs R1A, R1B, R1C 250 V AC 3000 mA
Relay outputs R1A, R1B, R1C 30 V DC 3000 mA
Relay outputs R2A, R2C 250 V AC 5000 mA
Relay outputs R2A, R2C 30 V DC 5000 mA
Relay outputs R3A, R3C 250 V AC 5000 mA
Relay outputs R3A, R3C 30 V DC 5000 mA
Output voltage <= power supply voltage
permissible temporary current boost 1.1 x In during 60 s (normal duty)
1.5 x In during 60 s (heavy duty)
Motor slip compensation Adjustable
Automatic whatever the load
Not available in permanent magnet motor law
Can be suppressed
Acceleration and deceleration ramps Linear adjustable separately from 0.01…9999 s
Physical interface Ethernet
2-wire RS 485
Braking to standstill By DC injection
protection type of ATV630C22N4 inverter Thermal protection: motor
Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
Transmission rate 10, 100 Mbits
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
frequency resolution Display unit: 0.1 Hz
Analog input: 0.012/50 Hz
Transmission frame RTU
electrical connection Control: removable screw terminals 0.5…1.5 mm²/AWG 20…AWG 16
Line side: screw terminal 2 x 150 mm²/2 x 350 kcmil
Motor: screw terminal 2 x 150 mm²/2 x 350 kcmil
connector type RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
RJ45 (on the remote graphic terminal) for Modbus serial
Data format of ATV630C22N4 inverter 8 bits, configurable odd, even or no parity
Type of polarization No impedance
exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
number of addresses 1…247 for Modbus serial
method of access Slave Modbus TCP
supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
local signalling 3 LEDs for local diagnostic
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
Width of ATV630C22N4 inverter 440 mm
Height of ATV630C22N4 inverter 1195 mm
Depth of ATV630C22N4 inverter 380 mm
Product weight 172 kg
Analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits
AI2 voltage analog input: – 10…10 V DC, impedance: 31.5 kOhm, resolution 12 bits
Discrete input number 8
discrete input type DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI1…DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
discrete input logic Positive logic (source) (DI1…DI8), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1…DI8), > 16 V (state 0), < 10 V (state 1)
Analogue output number 2
analogue output type Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits
Software-configurable current DQ-, DQ+: 30 V DC
Software-configurable current DQ-, DQ+: 100 mA
sampling duration 2 ms +/- 0.5 ms (DI1…DI4) – discrete input
5 ms +/- 1 ms (DI5, DI6) – discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input
10 ms +/- 1 ms (AO1) – analog output
accuracy of ATV630C22N4 inverter +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AO1, AO2: +/- 0.2 % for analog output
Relay output number 3
relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time of ATV630C22N4 inverter Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Isolation of ATV630C22N4 inverter Between power and control terminals
Maximum output frequency 500 kHz
Maximum input current 397.0 A
Variable speed drive application selection Building – HVAC Compressor centrifugal
Food and beverage processing Other application
Mining mineral and metal Fan
Mining mineral and metal Pump
Oil and gas Fan
Water and waste water Other application
Building – HVAC Screw compressor
Food and beverage processing Pump
Food and beverage processing Fan
Food and beverage processing Atomization
Oil and gas Electro submersible pump (ESP)
Oil and gas Water injection pump
Oil and gas Jet fuel pump
Oil and gas Compressor for refinery
Water and waste water Centrifuge pump
Water and waste water Positive displacement pump
Water and waste water Electro submersible pump (ESP)
Water and waste water Screw pump
Water and waste water Lobe compressor
Water and waste water Screw compressor
Water and waste water Compressor centrifugal
Water and waste water Fan
Water and waste water Conveyor
Water and waste water Mixer
Motor power range AC-3 110…220 kW at 380…440 V 3 phases
110…220 kW at 480…500 V 3 phases
Quantity per set 1
Enclosure mounting Wall mounted
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level 66 dB conforming to 86/188/EEC
power dissipation in W Forced convection: 5030 W
Natural convection: 451 W at 380 V, switching frequency 2.5 kHz
Volume of cooling air 860 m3/h
Operating position Vertical +/- 10 degree
maximum THDI <48 % full load conforming to IEC 61000-3-12
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -10…40 °C (without derating)
40…60 °C (with derating factor)
Ambient air temperature for storage -25…70 °C
operating altitude <= 1000 m without derating
1000…3000 m with current derating 1 % per 100 m
standards UL 508C
EN/IEC 61800-3
Environment 1 category C2 EN/IEC 61800-3
Environment 2 category C3 EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
Product certifications TÜV
CSA
UL
Marking of ATV630C22N4 inverter CE
Standards of ATV630C22N4 inverter UL 508C
EN/IEC 61800-3
EN/IEC 61800-3 environment 1 category C2
EN/IEC 61800-3 environment 2 category C3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
Overvoltage category III
Regulation loop Adjustable PID regulator
Noise level 73 dB
Pollution degree 2

FAQ ( frequently ask questions )

A: inquiry→quotation→confirm→send PI→make the payment→arrange the parts→delivery→receive the parts

A: By sea to your nearest port

By air to your nearest airport

By express (DHL,UPS,FEDEX,TNT,EMS)to your door

When your order shipping out . we will provide you a tracking number. then you can know clearly the status of the goods

A: Motsly parts we have stock before you want to book with us pls email us and confirm the delivery time and price. Usually 1-5 working days.

DHLAround 3-5 working days
FedExAround 3-5 working days
UPS/TNTAround 6-8 working days
EMSAround 10-15 working days
AIRAround 5-7 working days
SEAAround 15-30 working days

A: Of course, common products are allowed to be exchanged as long as you pay the freight and custom cost

A: Yes, we have warranty for our parts. 3 months for PCB, 2 years for original roller and other roller, 3-5 years for COMI roller and 1 year for Yaskawa inverter. Please contact us to get more information for other products

A: You can send it back to repair ,but the freight and repair charge will be paid by you.

A: TT, Western Union, Pay pal, You can choose a convinient way for you .

Kindly contact our staff to get more answers. Thanks for your cooperation!!!”

RElated Products

send your message to us