network number of phases 3 phases
motor power kW 7.5 kW
motor power hp 10 hp
supply voltage limits 323…528 V
supply frequency of ATV212HU75N4 50…60 Hz – 5…5 %
line current of ATV212HU75N4 11.7 A at 480 V
14.7 A at 380 V
range of product Altivar 212
product or component type Variable speed drive
product specific application of ATV212HU75N4 Pumps and fans in HVAC
communication port protocol of ATV212HU75N4 APOGEE FLN
LonWorks
BACnet
METASYS N2
Modbus
[Us] rated supply voltage 380…480 V – 15…10 %
EMC filter Class C2 EMC filter integrated
IP degree of protection IP21
apparent power 12.2 kVA at 380 V
continuous output current 16 A at 380 V
16 A at 460 V
maximum transient current 17.6 A for 60 s
speed drive output frequency 0.5…200 Hz
speed range 1…10
speed accuracy of ATV212HU75N4 +/- 10 % of nominal slip 0.2 Tn to Tn
local signalling 1 LED (red) for DC bus energized
output voltage of ATV212HU75N4 <= power supply voltage
isolation of ATV212HU75N4 Electrical between power and control
type of cable Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
electrical connection VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 16 mm² / AWG 6
tightening torque 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
2.5 N.m, 22 lb.in (L1/R, L2/S, L3/T)
supply Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection
sampling duration 2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
response time FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
accuracy +/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °C
linearity error VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for output
analogue output type FM switch-configurable voltage 0…10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0…20 mA, impedance: 970 Ohm, resolution 10 bits
discrete output type Configurable relay logic: (FLA, FLC) NO – 100000 cycles
Configurable relay logic: (FLB, FLC) NC – 100000 cycles
Configurable relay logic: (RY, RC) NO – 100000 cycles
minimum switching current 3 mA at 24 V DC for configurable relay logic
maximum switching current 5 A at 250 V AC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R)
discrete input type F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
discrete input logic Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
dielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminals
insulation resistance >= 1 mOhm 500 V DC for 1 minute
frequency resolution Display unit: 0.1 Hz
Analog input: 0.024/50 Hz
communication service Monitoring inhibitable
Read holding registers (03) 2 words maximum
Write multiple registers (16) 2 words maximum
Write single register (06)
Read device identification (43)
Time out setting from 0.1 to 100 s
option card Communication card for LonWorks
power dissipation in W 291 W
air flow 100 m3/h
functionality Mid
specific application HVAC
Variable speed drive application selection Building – HVAC Compressor for scroll
Building – HVAC Fan
Building – HVAC Pump
Motor power range AC-3 7…11 kW at 380…440 V 3 phases
7…11 kW at 480…500 V 3 phases
motor starter type Variable speed drive
discrete output number 2
analogue input number 2
analogue input type VIA switch-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0…6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 10 bits
analogue output number 1
physical interface 2-wire RS 485
connector type 1 open style
1 RJ45
transmission rate 9600 bps or 19200 bps
transmission frame RTU
number of addresses 1…247
data format 8 bits, 1 stop, odd even or no configurable parity
type of polarization No impedance
asynchronous motor control profile Voltage/frequency ratio – Energy Saving, quadratic U/f
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Flux vector control without sensor, standard
Voltage/frequency ratio, 5 points
Voltage/frequency ratio, 2 points
torque accuracy +/- 15 %
transient overtorque 120 % of nominal motor torque +/- 10 % for 60 s
acceleration and deceleration ramps Linear adjustable separately from 0.01 to 3200 s
Automatic based on the load
motor slip compensation Not available in voltage/frequency ratio motor control
Automatic whatever the load
Adjustable
switching frequency 6…16 kHz adjustable
12…16 kHz with derating factor
nominal switching frequency 12 kHz
braking to standstill By DC injection
network frequency 47.5…63 Hz
prospective line Isc 22 kA
protection type Overheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motor
width 180 mm
height 232 mm
depth 170 mm
net weight 6.45 kg
pollution degree 3 conforming to IEC 61800-5-1
IP degree of protection IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1
IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP21 conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
vibration resistance 1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8
shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27
environmental characteristic Classes 3C1 conforming to IEC 60721-3-3
Classes 3S2 conforming to IEC 60721-3-3
noise level 51 dB conforming to 86/188/EEC
operating altitude 1000…3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
<= 1000 m without derating
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
ambient air temperature for operation -10…40 °C (without derating)
40…50 °C (with derating factor)
operating position Vertical +/- 10 degree
product certifications of ATV212HU75N4 C-Tick
NOM 117
UL
CSA
marking of ATV212HU75N4 CE
standards of ATV212HU75N4 EN 61800-3
EN 61800-3 environments 1 category C1
IEC 61800-3 category C3
IEC 61800-5-1
IEC 61800-3 category C2
IEC 61800-3 environments 1 category C2
EN 61800-3 environments 2 category C2
EN 61800-3 environments 1 category C2
EN 61800-3 category C2
EN 61800-3 category C3
EN 61800-3 environments 2 category C3
IEC 61800-3 environments 1 category C3
UL Type 1
IEC 61800-3 environments 2 category C2
EN 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C1
EN 55011 class A group 1
EN 61800-3 environments 2 category C1
EN 61800-5-1
IEC 61800-3 environments 2 category C3
IEC 61800-3
IEC 61800-3 environments 1 category C1
assembly style of ATV212HU75N4 With heat sink
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
regulation loop of ATV212HU75N4 Adjustable PI regulator
ambient air temperature for storage -25…70 °C

FAQ ( frequently ask questions )

A: inquiry→quotation→confirm→send PI→make the payment→arrange the parts→delivery→receive the parts

A: By sea to your nearest port

By air to your nearest airport

By express (DHL,UPS,FEDEX,TNT,EMS)to your door

When your order shipping out . we will provide you a tracking number. then you can know clearly the status of the goods

A: Motsly parts we have stock before you want to book with us pls email us and confirm the delivery time and price. Usually 1-5 working days.

DHLAround 3-5 working days
FedExAround 3-5 working days
UPS/TNTAround 6-8 working days
EMSAround 10-15 working days
AIRAround 5-7 working days
SEAAround 15-30 working days

A: Of course, common products are allowed to be exchanged as long as you pay the freight and custom cost

A: Yes, we have warranty for our parts. 3 months for PCB, 2 years for original roller and other roller, 3-5 years for COMI roller and 1 year for Yaskawa inverter. Please contact us to get more information for other products

A: You can send it back to repair ,but the freight and repair charge will be paid by you.

A: TT, Western Union, Pay pal, You can choose a convinient way for you .

Kindly contact our staff to get more answers. Thanks for your cooperation!!!”

RElated Products

send your message to us