ATV212WD75N4 inverter, 75kw ATV212 spot free shipping

ATV212WD75N4 inverter, 75kw ATV212 spot free shipping

Share to:

Aditional Informations

PRODUCT INFORMATION OF SCHNEIDER ATV212WD75N4 inverter, 75kw inverter ATV212 spot free shipping

 

Main

Device short name ATV212
Product destination Asynchronous motors
Network number of phases 3 phases
motor power kW 75 kW
motor power hp 100 hp
Supply voltage limits 323…528 V
supply frequency 50…60 Hz – 5…5 %
line current 141.8 A at 380 V
111.3 A at 480 V
Range of product Altivar 212
Product or component type Variable speed drive
Product specific application Pumps and fans in HVAC
Communication port protocol BACnet
METASYS N2
Modbus
LonWorks
APOGEE FLN
[Us] rated supply voltage 380…480 V – 15…10 %
EMC filter Class C2 EMC filter integrated
IP degree of protection IP55
apparent power 105.3 kVA at 380 V
continuous output current 160 A at 380 V
160 A at 460 V
maximum transient current 176 A for 60 s
Speed drive output frequency 0.5…200 Hz
speed range 1…10
speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn
local signalling 1 LED (red) for DC bus energized
Output voltage <= power supply voltage
Isolation Electrical between power and control
type of cable Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
electrical connection VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 150 mm² (300 kcmil)
tightening torque 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
41 N.m, 360 lb.in (L1/R, L2/S, L3/T)
supply of ATV212WD75N4 Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection
sampling duration 2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
response time FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
accuracy of ATV212WD75N4 +/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °C
linearity error VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for output
analogue output type FM switch-configurable voltage 0…10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0…20 mA, impedance: 970 Ohm, resolution 10 bits
discrete output type of ATV212WD75N4 Configurable relay logic: (FLA, FLC) NO – 100000 cycles
Configurable relay logic: (FLB, FLC) NC – 100000 cycles
Configurable relay logic: (RY, RC) NO – 100000 cycles
minimum switching current 3 mA at 24 V DC for configurable relay logic
maximum switching current 5 A at 250 V AC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R)
discrete input type F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
discrete input logic Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
dielectric strength of ATV212WD75N4 3535 V DC between earth and power terminals
5092 V DC between control and power terminals
insulation resistance >= 1 mOhm 500 V DC for 1 minute
frequency resolution Display unit: 0.1 Hz
Analog input: 0.024/50 Hz
Communication service Write single register (06)
Time out setting from 0.1 to 100 s
Read device identification (43)
Write multiple registers (16) 2 words maximum
Monitoring inhibitable
Read holding registers (03) 2 words maximum
option card of ATV212WD75N4 Communication card for LonWorks
Functionality Mid
Specific application HVAC
Discrete output number 2
Analogue input number 2
analogue input type VIA switch-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0…6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 10 bits
Analogue output number 1
Physical interface 2-wire RS 485
Connector type 1 RJ45
1 open style
Transmission rate 9600 bps or 19200 bps
Transmission frame RTU
Number of addresses 1…247
Data format 8 bits, 1 stop, odd even or no configurable parity
Type of polarization No impedance
Asynchronous motor control profile Voltage/frequency ratio – Energy Saving, quadratic U/f
Flux vector control without sensor, standard
Voltage/frequency ratio, 5 points
Voltage/frequency ratio, 2 points
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Torque accuracy +/- 15 %
transient overtorque 120 % of nominal motor torque +/- 10 % for 60 s
Acceleration and deceleration ramps Linear adjustable separately from 0.01 to 3200 s
Automatic based on the load
Motor slip compensation Adjustable
Not available in voltage/frequency ratio motor control
Automatic whatever the load
switching frequency 6…16 kHz adjustable
8…16 kHz with derating factor
Nominal switching frequency 8 kHz
Braking to standstill By DC injection
Network frequency 47.5…63 Hz
Prospective line Isc 22 kA
protection type Overheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motor
Width of ATV212WD75N4 362 mm
Height of ATV212WD75N4 1000 mm
Depth of ATV212WD75N4 364 mm
pollution degree 3 conforming to IEC 61800-5-1
IP degree of protection IP55 conforming to EN/IEC 61800-5-1
IP55 conforming to EN/IEC 60529
vibration resistance 1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8
shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27
environmental characteristic Classes 3C1 conforming to IEC 60721-3-3
Classes 3S2 conforming to IEC 60721-3-3
noise level 63.7 dB conforming to 86/188/EEC
operating altitude 1000…3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
<= 1000 m without derating
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
ambient air temperature for operation -10…40 °C (without derating)
40…50 °C (with derating factor)
Operating position Vertical +/- 10 degree
Product certifications UL
NOM 117
CSA
C-Tick
Marking of ATV212WD75N4 CE
Standards of ATV212WD75N4 EN 61800-3 environments 2 category C2
IEC 61800-3 environments 2 category C3
IEC 61800-3 category C2
IEC 61800-3 category C3
EN 61800-3 environments 1 category C2
EN 61800-3
IEC 61800-5-1
EN 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C3
EN 61800-3 category C3
IEC 61800-3 environments 1 category C2
EN 61800-5-1
IEC 61800-3 environments 1 category C1
EN 61800-3 environments 2 category C1
EN 55011 class A group 1
IEC 61800-3
EN 61800-3 category C2
IEC 61800-3 environments 2 category C1
IEC 61800-3 environments 1 category C3
EN 61800-3 environments 1 category C1
IEC 61800-3 environments 2 category C2
Assembly style With heat sink
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Regulation loop Adjustable PI regulator
Ambient air temperature for storage -25…70 °C

FAQ ( frequently ask questions )

A: inquiry→quotation→confirm→send PI→make the payment→arrange the parts→delivery→receive the parts

A: By sea to your nearest port

By air to your nearest airport

By express (DHL,UPS,FEDEX,TNT,EMS)to your door

When your order shipping out . we will provide you a tracking number. then you can know clearly the status of the goods

A: Motsly parts we have stock before you want to book with us pls email us and confirm the delivery time and price. Usually 1-5 working days.

DHLAround 3-5 working days
FedExAround 3-5 working days
UPS/TNTAround 6-8 working days
EMSAround 10-15 working days
AIRAround 5-7 working days
SEAAround 15-30 working days

A: Of course, common products are allowed to be exchanged as long as you pay the freight and custom cost

A: Yes, we have warranty for our parts. 3 months for PCB, 2 years for original roller and other roller, 3-5 years for COMI roller and 1 year for Yaskawa inverter. Please contact us to get more information for other products

A: You can send it back to repair ,but the freight and repair charge will be paid by you.

A: TT, Western Union, Pay pal, You can choose a convinient way for you .

Kindly contact our staff to get more answers. Thanks for your cooperation!!!”

RElated Products

send your message to us