ATV630D75N4 inverter, 75kw ATV630 spot

ATV630D75N4 inverter, 75kw ATV630 spot

Share to:

Aditional Informations

PRODUCT INFORMATION OF SCHNEIDER ATV630D75N4 inverter, 75kw ATV630 spot

 

Main

Range of product Altivar Process ATV600
Product or component type Variable speed drive
Product specific application Process and utilities
Device short name ATV630
Variant of ATV630D75N4 inverter Standard version
Product destination Asynchronous motors
Synchronous motors
EMC filter of ATV630D75N4 inverter Integrated with 150 m conforming to EN/IEC 61800-3 category C3
IP degree of protection IP21 conforming to IEC 61800-5-1
IP21 conforming to IEC 60529
[Us] rated supply voltage 380…480 V
degree of protection UL type 1 conforming to UL 508C
Type of cooling Forced convection
supply frequency 50…60 Hz – 5…5 %
[Us] rated supply voltage 380…480 V – 15…10 %
motor power kW 75 kW (normal duty)
55 kW (heavy duty)
motor power hp 100 hp normal duty
75 hp heavy duty
line current of ATV630D75N4 inverter 131.3 A at 380 V (normal duty)
112.7 A at 480 V (normal duty)
98.9 A at 380 V (heavy duty)
86.9 A at 480 V (heavy duty)
Prospective line Isc 50 kA
apparent power 93.7 kVA at 480 V (normal duty)
72.2 kVA at 480 V (heavy duty)
continuous output current 145 A at 2.5 kHz for normal duty
106 A at 2.5 kHz for heavy duty
maximum transient current 159.5 A during 60 s (normal duty)
159 A during 60 s (heavy duty)
Asynchronous motor control profile Variable torque standard
Constant torque standard
Optimized torque mode
Synchronous motor control profile Permanent magnet motor
Synchronous reluctance motor
Speed drive output frequency 0.1…500 Hz
Nominal switching frequency 2.5 kHz
switching frequency 2.5…8 kHz with derating factor
2…8 kHz adjustable
safety function STO (safe torque off) SIL 3
Discrete input logic 16 preset speeds
Communication port protocol Ethernet
Modbus serial
Modbus TCP
option card of ATV630D75N4 inverter Slot A: communication module, Profibus DP V1
Slot A: communication module, PROFINET
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/EtherNet/IP
Slot A: communication module, CANopen daisy chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw terminals
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink
Mounting mode Wall mount
Network number of phases 3 phases
Discrete output number 0
discrete output type Relay outputs R1A, R1B, R1C 250 V AC 3000 mA
Relay outputs R1A, R1B, R1C 30 V DC 3000 mA
Relay outputs R2A, R2C 250 V AC 5000 mA
Relay outputs R2A, R2C 30 V DC 5000 mA
Relay outputs R3A, R3C 250 V AC 5000 mA
Relay outputs R3A, R3C 30 V DC 5000 mA
Output voltage <= power supply voltage
permissible temporary current boost 1.1 x In during 60 s (normal duty)
1.5 x In during 60 s (heavy duty)
Motor slip compensation Automatic whatever the load
Adjustable
Not available in permanent magnet motor law
Can be suppressed
Acceleration and deceleration ramps Linear adjustable separately from 0.01…9999 s
Physical interface Ethernet
2-wire RS 485
Braking to standstill By DC injection
protection type of ATV630D75N4 inverter Thermal protection: motor
Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
Transmission rate 10, 100 Mbits
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
frequency resolution Display unit: 0.1 Hz
Analog input: 0.012/50 Hz
Transmission frame RTU
electrical connection Control: removable screw terminals 0.5…1.5 mm²/AWG 20…AWG 16
Motor: screw terminal 95…120 mm²/AWG 3/0…250 kcmil
Line side: screw terminal 95…120 mm²/AWG 3/0…250 kcmil
connector type of ATV630D75N4 inverter RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
RJ45 (on the remote graphic terminal) for Modbus serial
Data format 8 bits, configurable odd, even or no parity
Type of polarization No impedance
exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
number of addresses 1…247 for Modbus serial
method of access Slave Modbus TCP
supply of ATV630D75N4 inverter External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
local signalling 3 LEDs for local diagnostic
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
Width of ATV630D75N4 inverter 290 mm
Height of ATV630D75N4 inverter 922 mm
Depth of ATV630D75N4 inverter 323 mm
Product weight 58 kg
Analogue input number 3
analogue input type AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits
AI2 voltage analog input: – 10…10 V DC, impedance: 31.5 kOhm, resolution 12 bits
Discrete input number 8
discrete input type DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
input compatibility DI1…DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
discrete input logic Positive logic (source) (DI1…DI8), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1…DI8), > 16 V (state 0), < 10 V (state 1)
Analogue output number 2
analogue output type Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits
Software-configurable current DQ-, DQ+: 30 V DC
Software-configurable current DQ-, DQ+: 100 mA
sampling duration 2 ms +/- 0.5 ms (DI1…DI4) – discrete input
5 ms +/- 1 ms (DI5, DI6) – discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input
10 ms +/- 1 ms (AO1) – analog output
accuracy of ATV630D75N4 inverter +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
linearity error of ATV630D75N4 inverter AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AO1, AO2: +/- 0.2 % for analog output
Relay output number 3
relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
refresh time of ATV630D75N4 inverter Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Isolation of ATV630D75N4 inverter Between power and control terminals
Maximum output frequency 500 kHz
Maximum input current 131.3 A
Variable speed drive application selection Compressor centrifugal Building – HVAC
Other application Food and beverage processing
Fan Mining mineral and metal
Pump Mining mineral and metal
Fan Oil and gas
Other application Water and waste water
Screw compressor Building – HVAC
Pump Food and beverage processing
Fan Food and beverage processing
Atomization Food and beverage processing
Electro submersible pump (ESP) Oil and gas
Water injection pump Oil and gas
Jet fuel pump Oil and gas
Compressor for refinery Oil and gas
Centrifuge pump Water and waste water
Positive displacement pump Water and waste water
Electro submersible pump (ESP) Water and waste water
Screw pump Water and waste water
Lobe compressor Water and waste water
Screw compressor Water and waste water
Compressor centrifugal Water and waste water
Fan Water and waste water
Conveyor Water and waste water
Mixer Water and waste water
Motor power range AC-3 55…100 kW at 380…440 V 3 phases
55…100 kW at 480…500 V 3 phases
Quantity per set 1
Enclosure mounting Wall mounted
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
noise level of ATV630D75N4 inverter 62.4 dB conforming to 86/188/EEC
power dissipation in W Natural convection: 174 W at 380 V, switching frequency 2.5 kHz
Forced convection: 1369 W at 380 V, switching frequency 2.5 kHz
Volume of cooling air 295 m3/h
Operating position Vertical +/- 10 degree
maximum THDI <48 % from 80…100 % of load conforming to IEC 61000-3-12
electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27
relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -15…50 °C (without derating)
50…60 °C (with derating factor)
Ambient air temperature for storage -40…70 °C
operating altitude <= 1000 m without derating
1000…4800 m with current derating 1 % per 100 m
standards of ATV630D75N4 inverter UL 508C
EN/IEC 61800-3
Environment 1 category C2 EN/IEC 61800-3
Environment 2 category C3 EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
Product certifications CSA
ATEX zone 2/22
TÜV
ATEX INERIS
UL
DNV-GL
Marking of ATV630D75N4 inverter CE
Standards of ATV630D75N4 inverter UL 508C
EN/IEC 61800-3
EN/IEC 61800-3 environment 1 category C2
EN/IEC 61800-3 environment 2 category C3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
Overvoltage category III
Regulation loop Adjustable PID regulator
Noise level of ATV630D75N4 inverter 62.4 dB
Pollution degree 2

FAQ ( frequently ask questions )

A: inquiry→quotation→confirm→send PI→make the payment→arrange the parts→delivery→receive the parts

A: By sea to your nearest port

By air to your nearest airport

By express (DHL,UPS,FEDEX,TNT,EMS)to your door

When your order shipping out . we will provide you a tracking number. then you can know clearly the status of the goods

A: Motsly parts we have stock before you want to book with us pls email us and confirm the delivery time and price. Usually 1-5 working days.

DHLAround 3-5 working days
FedExAround 3-5 working days
UPS/TNTAround 6-8 working days
EMSAround 10-15 working days
AIRAround 5-7 working days
SEAAround 15-30 working days

A: Of course, common products are allowed to be exchanged as long as you pay the freight and custom cost

A: Yes, we have warranty for our parts. 3 months for PCB, 2 years for original roller and other roller, 3-5 years for COMI roller and 1 year for Yaskawa inverter. Please contact us to get more information for other products

A: You can send it back to repair ,but the freight and repair charge will be paid by you.

A: TT, Western Union, Pay pal, You can choose a convinient way for you .

Kindly contact our staff to get more answers. Thanks for your cooperation!!!”

RElated Products

send your message to us