TM262M25MESS8T plc, M262 series PLC motion controller spot
- Name: TM262M25MESS8T plc, M262 series PLC motion controller spot
- Brand: Schneider
- Model: TM262M25MESS8T
- MOQ. : 1
- Warranty Time : 1 Year
- Certificates: ISO9001
- Price:
- Contact Person: Ms. Ma Meiying
- Email: sales@upalhd.com
- Email: sales.upalhd@hotmail.com
- Mobile-1: +86-16622133544
- Phone-2: +86-16602136043
Share to:
- Contact Peroson: Ms. Raihana
- Email: sales@upalhd.com
- Email: salse.upalhd@hotmail.com
- Phone-1: +86-16602136043
- Phone-2: +86-15557972300
Aditional Informations
PRODUCT INFORMATION OF SCHNEIDER TM262M25MESS8T plc, M262 series PLC motion controller spot
Range of product | Logic/motion controller – Modicon M262 |
---|---|
Product or component type | Motion controller |
[Us] rated supply voltage | 24 V DC – 15…20 % |
Discrete I/O number | 8 |
Upstream connectivity of TM262M25MESS8T plc | IIoT-ready machine to cloud Connected machine to plant |
supply voltage limits | 20.4…28.8 V DC |
PLC Power Consumption | 82 W |
Inrush current | 40 A |
Overvoltage protection | With |
discrete input number | 4, discrete input fast input conforming to IEC 61131-2 Type 1 |
Discrete input voltage | 24 V |
Discrete input voltage type | DC |
discrete input logic | Sink |
voltage state 1 guaranteed | >= 15 V for DC |
voltage state 0 guaranteed | <= 5 V for DC |
discrete input current | 7.5 mA for fast input |
input impedance | 2.81 kOhm for input |
response time | <= 1 µs turn-on, I0…I3 terminal(s) for fast input <= 1 µs turn-off, I0…I3 terminal(s) for fast input <= 1 µs turn-on, Q0…Q3 terminal(s) for fast output <= 1 µs turn-off, Q0…Q3 terminal(s) for fast output |
configurable filtering time | 0.001 ms for fast input 0.002 ms for fast input 0.005 ms for fast input 0.01 ms for fast input 0.05 ms for fast input 0.1 ms for fast input 0.5 ms for fast input 1 ms for fast input 4 ms for fast input 12 ms for fast input |
discrete output number | 4 transistor fast output |
discrete output voltage | 24 V DC |
discrete output current | 0.5 A for fast output (Q0…Q3) |
Discrete output type | Transistor |
Discrete output logic | Source |
output voltage limits | 30 V DC |
maximum current per output common | 0.5 A with Q0…Q3 for fast output |
maximum output frequency | 300 kHz |
accuracy | +/- 0.1 % at 0.02…0.1 kHz for fast output +/- 1 % at 0.1…1 kHz for fast output |
maximum leakage current | 10 µA for output |
maximum tungsten load | <1.5 W |
protection type | Short-circuit and overload protection with automatic reset Reverse polarity protection Short-circuit protection |
reset time of TM262M25MESS8T plc | 200 ms automatic reset fast output |
maximum number of I/O expansion module | 7TM3 IO module (remote I/O-Architecture) 7TM3 IO module (local I/O-Architecture) 64TM3, TM5 or TM7 IO island (distributed I/O-Architecture) |
execution time for 1 KInstruction | 0.003 ms |
memory capacity | 32 MB for program RAM 32 MB for OS/website RAM 192 MB for system memory RAM |
data backed up | 1 GB built-in flash memory for backup of user programs |
data storage equipment | <= 32 GB SDHC card (optional) |
backup time | 1000 h at 25 °C |
Application structure | 8 event tasks 4 cyclic master tasks 3 cyclic master tasks + 1 freewheeling task 8 external event tasks |
Realtime clock | With |
clock drift of TM262M25MESS8T plc | <= 10 s/month at 25 °C |
cycle time of TM262M25MESS8T plc | 0.5 ms |
positioning functions | Libraries axes coordinated function Libraries axes synchronous function Sercos 3 motion bus function |
integrated connection type | Ethernet/Sercos 1 with RJ45 connector and 10/100BASE-T interface Ethernet 2 with 2 RJ45 connector and 100/1000BASE-T interface Serial link with RJ45 connector and RS232/RS485 interface 1 encoder with female SUB-D 15 connector and RS422/SSI interface Smart Communication Bus TM3 IO bus USB type mini B |
transmission rate of TM262M25MESS8T plc | 115 kbit/s for bus length of 15 m for RS485 115 kbit/s for bus length of 3 m for RS232 480 Mbit/s for bus length of 3 m for USB 10/100 Mbit/s for Ethernet1 10/100/1000 Mbit/s for Ethernet2 |
communication port protocol | EtherNet/IP adapter EtherNet/IP scanner Modbus TCP client/server Modbus TCP IO scanner Modbus TCP NVL Ethernet RSTP Modbus SL client/server Modbus SL IO scanner Modbus SL modem management Machine Expert ASCII manager ASCII modem management Sercos III master |
maximum number of connected devices | EtherNet/IP: 64 Modbus TCP: 64 Modbus TCP/EtherNet/IP: 128 |
Communication service | MQTTs OPC UA server (Encrypt) OPC UA client (Encrypt) HTTPs Methods (API) Web server Web visu TLS 1.2 TLS 1.3 SNTP NTP client/server FTP client/server FTPs server SQL client (remote access) DHCP client DHCP server DNS client POP3s client SMTP client SNMP client/server |
local signalling of TM262M25MESS8T plc | 1 LED (green/red) for PWR 1 LED (green/red) for RUN 1 LED (green/red) for ERROR (fault) 1 LED (green/red) for stop forced 1 LED (green/red) for I/O error (I/O) 1 LED (green/orange) for SD card activity 1 LED (green/orange) for SL activity 1 LED (green/red) for ETH1 state 1 LED (green/red) for ETH2 state 1 LED (green/red) for EIP MS 1 LED (green/red) for EIP NS 1 LED (green/red) for Sercos |
electrical connection | Removable spring terminal blockfor inputs and outputs removable spring terminal blockfor connecting the 24 V DC power supply |
product compatibility | External encoder 5/24 V DC no encoder power supply |
maximum cable distance between devices | Shielded cable: <3 m for fast input Shielded cable: <3 m for fast output Unshielded cable: <50 m for input Unshielded cable: <50 m for output Shielded cable: <30 m for RS485 link Shielded cable: <15 m for RS232 |
insulation of TM262M25MESS8T plc | Between fast input and internal logic at 550 V AC Non-insulated between inputs Between output and internal logic at 550 V AC Non-insulated between outputs Between input and output at 550 V AC Between supply and internal logic at 550 V AC Non-insulated between supply and ground |
Encoder type of TM262M25MESS8T plc | Incremental encoder |
surge withstand | 1 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 0.5 kV relay output differential mode conforming to EN/IEC 61000-4-5 1 kV input common mode conforming to EN/IEC 61000-4-5 1 kV transistor output common mode conforming to EN/IEC 61000-4-5 |
mounting support | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit |
Height of TM262M25MESS8T plc | 100 mm |
Depth of TM262M25MESS8T plc | 90 mm |
Width of TM262M25MESS8T plc | 125 mm |
Product weight | 0.67 kg |
standards of TM262M25MESS8T plc | UL 61010-1 UL 61010-2-201 CSA C22.2 No 61010-1 CSA C22.2 No 61010-2-201 CSA C22.2 No 213 ANSI/ISA 12-12-01 EN 61131-2 |
Product certifications of TM262M25MESS8T plc | CE cULus cULus HazLoc Class I Division 2 CSA 22-2 No 213 RCM EAC Achilles KC |
resistance to electrostatic discharge | 4 kV on contact conforming to EN/IEC 61000-4-2 8 kV on air conforming to EN/IEC 61000-4-2 |
resistance to electromagnetic fields | 10 V/m 80 MHz…1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2 GHz…3 GHz conforming to EN/IEC 61000-4-3 |
resistance to fast transients | 2 kV (power lines) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4 1 kV (input) conforming to EN/IEC 61000-4-4 1 kV (transistor output) conforming to EN/IEC 61000-4-4 |
resistance to conducted disturbances | 10 V 0.15…80 MHz conforming to EN/IEC 61000-4-4 3 V 0.1…80 MHz 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) |
electromagnetic emission | Conducted emissions – test level: 120…69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions – test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Radiated emissions – test level: 40 dBµV/m at 30…230 kHz conforming to EN/IEC 55011 Conducted emissions – test level: 79…63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions at 230…1000 MHz conforming to EN/IEC 55011 |
Immunity to microbreaks | 0.01 ms |
ambient air temperature for operation | -20…60 °C (horizontal installation) -20…50 °C (vertical installation) -20…45 °C (flat mounting) |
Ambient air temperature for storage | -40…85 °C |
relative humidity | 10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage) |
IP degree of protection | IP20 |
Pollution degree | 2 |
Operating altitude | 0…2000 m |
Storage altitude | 0…3000 m |
vibration resistance | 3.5 mm at 2…8.4 Hz on symmetrical rail 1 gn at 8.4…200 Hz on symmetrical rail 3.5 mm at 2…8.4 Hz on panel mounting 1 gn at 8.4…200 Hz on panel mounting |
shock resistance of TM262M25MESS8T plc | 15 gn for 11 ms |
FAQ ( frequently ask questions )
A: inquiry→quotation→confirm→send PI→make the payment→arrange the parts→delivery→receive the parts
A: By sea to your nearest port
By air to your nearest airport
By express (DHL,UPS,FEDEX,TNT,EMS)to your door
When your order shipping out . we will provide you a tracking number. then you can know clearly the status of the goods
A: Motsly parts we have stock before you want to book with us pls email us and confirm the delivery time and price. Usually 1-5 working days.
DHL | Around 3-5 working days |
---|---|
FedEx | Around 3-5 working days |
UPS/TNT | Around 6-8 working days |
EMS | Around 10-15 working days |
AIR | Around 5-7 working days |
SEA | Around 15-30 working days |
A: Of course, common products are allowed to be exchanged as long as you pay the freight and custom cost
A: Yes, we have warranty for our parts. 3 months for PCB, 2 years for original roller and other roller, 3-5 years for COMI roller and 1 year for Yaskawa inverter. Please contact us to get more information for other products
A: You can send it back to repair ,but the freight and repair charge will be paid by you.
A: TT, Western Union, Pay pal, You can choose a convinient way for you .
Kindly contact our staff to get more answers. Thanks for your cooperation!!!”